Technical Specifications
Nominal power supply
power supply 100÷240 Vca
power supply 21÷48 Vca/cc
Power consumption
7 W a 100 Vca
10 W a 240 Vca
4 W a 21 Vca / Vdc
5 W a 48 Vca / Vdc
Ambient operating conditions
Temperature: 0 ÷ 50 °C
Humidity: 45 ÷ 85% UR (without condensation)
Input
T/C tipo K
T/C tipo J
T/C type N
T/C type T
T/C type R
T/C type S
T/C type B
T/C type E
Pt100
Pt1000
0 ÷ 20 mA
4 ÷ 20 mA
0 ÷ 5 Volt
1 ÷ 5 Volt
0 ÷ 10 Volt
2 ÷ 10 Volt
Accuracy (*)
(*) @25°C
ingresso RTD: ±0,2% v.f.s
ingresso lineare (mA/Volt): ±0,2% v.f.s
ingresso Termocoppia: ±0,2°C (compensazione automatica del giunto freddo)
*accuratezza della misura a 25°C
Regulation output
4 different types of output can be selected when ordering:
SPDT relay (maximum load 5 A @ 250 Vca)
logic (15 Vdc max. 35 mA)
continuous output in Volts (0 / 2 ÷ 10 V) or in mA (0 / 4 ÷ 20mA) with selection by means of jumper on instrument's electronic board
servovalve control by means of 2 SPST relays (maximum load 3 A @ 250 Vca)
Power for two-wire transmitter
24Vdc max. 25mA
Digital input
Opto-isolated 2.5 kVolt
3 different operating modes can be programmed:
switching between two different Set Points
Automatic/Manual switching
keyboard lockout
Alarms
2 with SPST relay output (maximum load 3 A @ 250 Vca)
Serial interface
RS485 opto-isolated 2.5 kVolt
communications protocol: Modbus RTU
baud rate: 2.400, 4.800, 9.600, 19.200bps
access (reading / writing) to all regulator parameters
Type of display
4 digit a 7 segmenti (verde per PV e arancione per SV)
Other characteristics
manual or automatic control
Autotuning
Set Point ramp function
6 levels of access to programmable parameters
operational limitation of maximum / minimum Set Point
limitation of maximum power applicable to load
control mode: heating or cooling
International protection marking (*)
(*) According to IEC 60529
IP65
Front panel IP65
Installation category and degree of pollution
II
Dimensions
48 mm x 48 mm x 100 mm (model CH102)
48 mm x 96 mm x 100 mm (model CH402)
Panel cut-out
45 mm x 45 mm (CH102 model)
92 mm x 45 mm (model CH402)
Packaging
operator's manual in Italian
Volt input adapter
250Ω shunt resistance for input in mA
panel mounting strap
Programming software
ConfCH