You are now in our product catalog
Italiano | Deutsch | Français

IOCT - Rev. 0

EVOMINI IOCT
Signal converter for thermocouple temperature sensors with IO-Link interface (Cold Junction compensation INTERNAL)
Can be configured in three operating modes: IO-Link, 4÷20mA loop powered and switching output with alarm thresholds (SIO). Moulded body with dual M12 connector and IP67 protection degree. External influences such as ambient temperature, vibrations, moisture and EMC interference have minimal influence on the measurement thanks to the compact and robust design. Compatible with Italcoppie TCSV12 sensors series.
Need Help?
Sales Team
We will get back to you within 2 business days
Technical specifications
Electrical technical data for thermocouple Evomini IO-Link devices
Ambient temperature
-40 ÷70°C
Storage temperature
-40 ÷70°C
Operating humidity
0 ÷100%
Operating Voltage
18÷30 Vdc reverse polarity protection (IO-Link operating mode)
8÷32 Vdc reverse polarity protection (Loop Powered operating mode)
Current consumption
0.65 W (IO-Link operating mode) 0.8 W (SIO operating mode)
Input/Output insulation
None
Sensor input signal filter (*)
(*) time to reach 90% of signal
Configurable from 0.1s to 3.7s
Output signal type
Configurable between: 4÷20mA analogue signal; IO-Link; switching PNP or NPN output (SIO);
Permitted load
727Ω @ 24 Vdc [Rload= (Vpw. - 8) / 0,022] (Loop Powered operating mode)
Sensor break or short-circuit monitoring
In accordance with NAMUR NE43, selectable between:
Upper scale (≥ 21.0 mA)
Lower scale (≤ 3,6 mA)
(Loop Powered operating mode )
Communication interface
IO-Link Vers. 1.1 (COM2 - 38,4Kbaud)
M12x1 - 4 pos. A-coded
IO-Link Smart Sensor Profile (2nd ed.)
In accordance with SSP type 3.1
Switching output (*)
(*) SIO operating mode
NO/NC programmable, PNP/NPN
Overload and short circuit protection
Hysteresis or window function
Programmable output activation/deactivation delay
RGB LED for output status signaling (configurable color for OFF state and ON state)
Maximum current: 250mA
Display elements (*)
(*) IO-Link operating mode
Green color LED (IO-Link), RGB LED with configurable color (Locator), RGB LED with configurable color (SIO)
Temperature influence (*)
(*) deviation from 20°C
Maximum value between ±0,3°C/25°C and ±0,3% of span/25°C (Loop powered operating mode)
±0,3°C/25°C in the range 200...1000°C (IO-Link and SIO operating mode)
Long-term stability
Maximum 0.1% of span per year
Linear error
Negligible
Sensor error compensation
Offset or over two points
EMC
In accordance with EN 61326-1 (CE)
In accordance with BS EN 61326-1 (UKCA)
Input impedance
> 10 MΩ
Maximum loop resistance for both wire
10 KΩ (including T/C sensor)
Input
T/C type B
T/C type E
T/C tipo J
T/C tipo K
T/C type N
T/C type R
T/C type S
T/C type T
Cold junction compensation (*)
(*) Range -50÷400°C
Selectable between:
Internal
Fixed
Cold junction accuracy
±0,1°C + error of Pt1000 class A
Measurement range
T/C B: 400 ÷ 1810°C
T/C E: -260 ÷ 990°C
T/C J: -200 ÷ 1190°C
T/C K: -260 ÷ 1290°C
T/C N: -260 ÷ 1290°C
T/C R: -40 ÷ 1740°C
T/C S: -40 ÷ 1740°C
T/C T: -260 ÷ 390°C
Accuracy @25°C for IO-Link modality (*)
(*) Without cold junction and sensor error (thermocouple K class 2)
T/C B: ±2,0°C
T/C E: ±1.0°C
T/C J: ±1.0°C
T/C N: ±2.0°C (-260 ÷ -100°C) / ±1.0°C (-100 ÷ 1290°C)
T/C R: ±2.0°C
T/C S: ±2.0°C
T/C T: ±2.0°C
Accuracy @25°C for Loop Powered modality (*)
(*) Without cold junction and sensor error (thermocouple K class 2)
T/C B: maximum value between ±2.0°C and ±0.2% of span
T/C E: maximum value between ±1.0°C and ±0.2% of span
T/C J: maximum value between ±1.0°C and ±0.2% of span
Maximum value between ±1.0°C and ±0.2% of span
T/C N: maximum value between ±2.0°C (-260 ÷ -100°C) / ±1.0°C (-100 ÷ 1290°C) and ±0.2% of span
T/C R: maximum value between ±2.0°C and ±0.2% of span
T/C S: maximum value between ±2.0°C and ±0.2% of span
T/C T: maximum value between ±2.0°C and ±0.2% of span
Minimum span of signal retransmission (*)
(*) Loop Powered operating mode
T/C B: 700°C
T/C R, S: 300°C
T/C E, J, K, T: 50°C
T/C N: 100°C
Connection body material
THERMOPLASTIC
Type of connector
Female 4-pin connector (INPUT SENSOR), 4-pin male connector (OUTPUT), both with M12x1 metal screw lock (in accordance with IEC 61076-2-101)
International protection marking (*)
(*) According to IEC 60529
IP67
Programming
With any IO-Link programmation platform and the relative master.
Factory default
Loop Powered operating: (4÷20)mA output / Range 0÷1000°C / Sensor type T/C K / Sensor break ≥21mA / Sensor short-circuit ≤3.6mA
Switching output operating mode (SIO): PNP type output with hysteresis function NO, SP=800°C, RSP=700°C, no delay, output status signaling: LED color red
Media
QR code